11KV Copper Cable

Send Inquiry
11KV Copper Cable
Details
This 11kV copper cable is designed for medium-voltage power distribution where stable electrical performance, insulation protection and mechanical durability all need to be considered together.
Category
Medium Voltage Cable
Share to
Description

Product Overview

 

This 11kV copper cable is designed for medium-voltage power distribution where stable electrical performance, insulation protection and mechanical durability all need to be considered together.
The cable uses a Class 2 copper conductor with XLPE insulation. The insulation system includes conductor shielding and insulation shielding, followed by a copper tape metal shield. A galvanized steel wire armor provides additional mechanical protection, while the outer sheath is made from UV-resistant, flame-retardant LSZH material.
The construction can be adjusted according to the project specification. The technical data shown on this page uses 3×240 mm² as an example and does not represent the only available size.
For projects with different voltage levels, conductor cross-sections, installation conditions or environmental requirements, Huayu's technical team can confirm the appropriate construction before production.

 

Cable Construction

 

Conductor

Class 2 copper conductor

Insulation

XLPE, with conductor shield and insulation shield

Metal shield

Copper tape shield

Isolation

LSZH

Armor

Galvanized steel wire armor

Outer sheath

UV-resistant, flame-retardant LSZH

Cable identification

Three cores, identified by Yellow, Green and Red

Applicable standards

IEC 60502-2 and IEC 60228:2023

 

Key Features

 

The XLPE insulation system is designed for medium-voltage operation and provides the electrical insulation required between the conductor and the surrounding layers.

The copper tape shield forms part of the cable's electrical shielding system. It also provides a defined metallic layer around the insulated cores, which is important when the cable is used in a medium-voltage distribution system.

Galvanized steel wire armor adds mechanical protection to the cable. This is useful where the cable may be exposed to pulling forces, impact or other physical stress during installation and operation.

The LSZH outer sheath is UV-resistant and flame-retardant. This makes the cable suitable for installations where low-smoke, halogen-restricted materials are specified, particularly in locations where fire safety and personnel protection are important considerations.

 

Applications and Practical Value

 

This cable is mainly used in medium-voltage power distribution and industrial electrical systems.

For industrial plants, it can be used for power distribution between substations, switchgear and major electrical equipment. The armored construction helps protect the cable where the installation route is exposed to mechanical stress.

For outdoor installations, the UV-resistant sheath is useful where the cable is exposed to sunlight for extended periods. The cable construction can also be considered for industrial sites with demanding environmental conditions, subject to the actual project requirements.

For facilities with stricter smoke and halogen requirements, the LSZH sheath provides an alternative to conventional PVC sheath materials. This can be relevant in enclosed or populated areas where smoke and corrosive gases during a fire are major concerns.

The cable can also be specified for projects where several requirements need to be considered at the same time - medium-voltage performance, mechanical protection, flame retardancy and outdoor exposure. Instead of selecting each feature separately, the complete cable construction is reviewed against the actual installation conditions.

 

Application

 

MV application

 

Certificate

 

ISO Quality Management System Certificate
Verification to Standard: IEC 60502-2:2020, EN IEC 61000-6-1:2019,
EN IEC 61000-6-3:2021

 

certificate 02

 

1.Construction

S/N

Construction

Requirement

product-716-453

1

Conductor

2 Class 2 copper conductor

2

Insulation

+TR-XLPE+Conductor shield, XLPE insulation and insulation shield triple extrusion

3

Metal shield

Copper tape shield

4

Isolation

LSZH

5

Armor

Galvanized steel wire armor

6

Outer Sheath

UV-resistant, Flame-retardant LSZH

2. Cable identification

Core identification: Three cores: Yellow, Green, Red

Sheath color: Black

3. Standard compliance

IEC 60502-2, IEC 60228:2023

4.Application

S/N

Item

Technical requirement

1

Rated voltage

AC 8.7/15kV

2

Operating temperature

'-15~90℃

3

flame-retardant properties

12D

S/N

No. of cores × sectional area

Structure of conductor

Approx. dia. of conductor

Nominal thk. of insulation

Nominal thk.of sheath

Approx. OD of cable

Approx. weight of cable

 
 

no.× sqmm

no./mm

mm

mm

mm

mm

kg/km

 

1

3X240

36/2.94

18.6

4.5

3.15

3.6

84.2

14068

5. Electrical characteristics

S/N

No. of cores × sectional area ×

Max. DC resistance of conductor@20℃
20℃

Voltage withstand test

 

no.× sqmm

Ω/km

kV/min,no breakdown

1

3X240

0.124

34.6

 

Why Huayu Cable

 

Huayu Cable has been manufacturing wire and cable products since 2004. The company operates a production base of more than 258,000 m² and has developed 38 main product series with more than 8,000 specifications.

 

For medium-voltage cable projects, the benefit is not simply having different cable sizes available. A project may involve several cable types, different installation conditions and different certification requirements at the same time. Huayu's production, technical and sales teams can work together from the quotation stage to confirm the construction before the order enters production.

 

Huayu also maintains certification and testing capabilities covering a range of international and industry requirements, including ABS, CCS, DNV, LR, EAC/GOST, IEC, TÜV and CE, depending on the product and project specification.

1

 

FAQs

 

Q: Why use copper tape shielding in an 11kV cable?

A: The copper tape shield forms part of the cable's metallic shielding system and helps control the electrical field around the insulated conductor. The exact shielding and earthing arrangement should be confirmed according to the cable design and project requirements.

Q: What is the purpose of galvanized steel wire armor?

A: The steel wire armor provides additional mechanical protection. It is useful when the cable route may expose the cable to pulling forces, impact or other physical stress.

Q: Is this cable suitable for outdoor installation?

A: The example specification uses a UV-resistant outer sheath, which can be used for outdoor applications where the cable is exposed to sunlight. The complete installation conditions should still be reviewed before selecting the final cable construction.

Q: Can Huayu produce other 11kV cable constructions?

A: Yes. Cable construction can be discussed according to conductor size, insulation system, shielding, armor, sheath material, installation method and applicable standards. The final design is confirmed before production.

 

Hot Tags: 11kv copper cable, China 11kv copper cable manufacturers, suppliers, factory

Send Inquiry