Products Description
4 pair instrument cable is multi-twisted-pair signal cable with four pairs of conductors. It transmits four separate measurement and control signals for field sensors and transmitters.
Available shielded or unshielded. Shielded version reduces crosstalk between pairs. Used for multi-channel 4-20mA and RS-485 wiring in PLC and DCS industrial control systems.
|
Rated Voltage |
300/500V |
|
Conductor |
0.5mm², 0.75mm², 1.0mm², 1.5mm² |
|
Temperature Range |
-20℃ ~ +80℃ |
|
Standards |
IEC 60228, EN 50288-7 |
|
Core structure |
4 twisted pairs |
Application

Certificate
ISO Quality Management System Certificate
Verification to IEC 60227-5:2024,
EN IEC 61000-6-1:2019, EN IEC 61000-6-3:2021

|
1.Construction |
|||||||
|
S/N |
Construction |
Requirement |
|
||||
|
1 |
Conductor |
2 Class 2 copper conductor |
|||||
|
2 |
Insulation |
XLPE |
|||||
|
3 |
Individual Shield |
+ aliminum-plastic composite tape + drain wire |
|||||
|
4 |
Overall shield |
+ aliminum-plastic composite tape + drain wire |
|||||
|
5 |
Isolation |
PVC |
|||||
|
6 |
Armor |
Galvanized steel wire armor |
|||||
|
7 |
Sheath |
Rodent and ant proof, Flame Retardant PVC |
|||||
|
2. Cable identification Red, White + number code Sheath color: Black 3. Standard compliance GB/T 34016-2017, IEC 60332-3-22, TICW/06-2009, Q/WHY 09 |
|||||||
|
4.Application |
|||||||
|
S/N |
Item |
Technical requirement |
|||||
|
1 |
Rated voltage |
AC 300/500V |
|||||
|
2 |
Operating temperature |
'-15~90℃ |
|||||
|
S/N |
No. of cores × sectional area |
Structure of conductor |
Approx. dia. of conductor |
Nominal thk. of insulation |
Nominal thk.of sheath |
Approx. OD of cable |
Approx. weight of cable |
|
no.× sqmm |
no./mm |
mm |
mm |
mm |
mm |
kg/km |
|
|
1 |
5×2×1.5 |
7/0.52 |
1.56 |
0.6 |
1.4 |
23.3 |
1049 |
|
2 |
10×2×1.5 |
7/0.52 |
1.56 |
0.6 |
1.5 |
30.9 |
1521 |
|
5. Electrical characteristics |
|||||||
|
S/N |
No. of cores × sectional area × |
Max. DC resistance of conductor@20℃ |
Voltage withstand test |
||||
|
no.× sqmm |
Ω/km |
kV/min,no breakdown |
|||||
|
1 |
5×2×1.5 |
12.1 |
1/1 |
||||
|
2 |
10×2×1.5 |
12.1 |
1/1 |
||||
Huayu 4 Pair Instrument Cable Advantages
- 4-pair integrated, supports 4 signal loops, saves tray space & installation cost70dB+ shielding, suppresses EMI from motors and converters
- Capacitance ≤200pF/100m, stable 4-20mA signal up to 800m
- RS-485 transmission up to 1200m with correct wiring
- 55dB+ crosstalk reduction, prevents signal interference between pairs
- Insulation resistance ≥5000MΩ·km, low signal leakage for long-term use
- Full-batch pre-shipment tests; shielded/unshielded, LSZH flame-retardant optional

FAQs
1.When to use 4 pair instrument cable?
For multi-channel 4-20mA sensors and RS-485, ideal for multi-point PLC and DCS instrument loops.
2.What is the benefit of four-pair structure?
One cable carries 4 signal loops, saves tray space and cuts installation work.
3.What is its maximum transmission distance?
4-20mA signal stable up to 800m; RS-485 can reach 1200m with proper installation.
Hot Tags: 4 pair instrument cable, China 4 pair instrument cable manufacturers, suppliers, factory, 2 Pair Instrument Cable, 4 Pair Instrument Cable, Fire Rated Instrumentation Cable, Multicore Instrumentation Cable, Multipair Instrumentation Cable, Shielded Instrumentation Cable