BS 5467 Armored Power Cable

Send Inquiry
BS 5467 Armored Power Cable
Details
2 Class 2 tinned copper conductor. Tinning slows down oxidation, so the conductor holds up better than bare copper in damp, salt-heavy, or long-term buried conditions.
Category
Low Voltage Cable
Share to
Description

Products Description

 

Conductor

2 Class 2 tinned copper conductor. Tinning slows down oxidation, so the conductor holds up better than bare copper in damp, salt-heavy, or long-term buried conditions.

 

Insulation and Sheath

XLPE insulation, with PVC/ST2 bedding and outer sheath - a standard, well-proven combination for medium-voltage distribution work.

 

Armor and Earthing

Galvanized steel wire armor with a galvanized steel tape counter helix, plus a copper earth wire woven into the armor layer. On a ground fault, that earth wire gives current a low-impedance path back to source, which speeds up fault clearance and lowers touch-voltage risk on site.

 

Rated Voltage and Temperature

AC 0.6/1kV, rated for -15°C to 90°C operation, covering most industrial and outdoor conditions.

 

Installation Note

Minimum bending radius is 12 times the cable's outer diameter - worth factoring into conduit or trench layout before ordering.

 

Where It's Used

Coastal substations and port facilities, where salt exposure shortens the service life of unprotected conductors. Direct-buried distribution runs, where the armor resists damage from soil movement and rodents. Sites with strict earthing requirements, where the built-in earth wire simplifies compliance without adding a separate conductor.

 

Why Source This From Us

Each reel is tested against the voltage withstand and resistance figures in the spec sheet before shipping, with test reports kept on file per batch. If your project needs a different core count, conductor size, or armor type, we requote from our own factory rather than reselling fixed stock, usually within 2 working days.

 

Application

 

product-1200-800

 

Certificate

 

ISO Quality Management System Certificate

IEC 60502-1:2020, EN IEC 61000-6-1:2019,

EN IEC 61000-6-3:2021

 

certificate 05

 

1.Construction

S/N

Construction

Requirement

product-680-474

1

Conductor

2 Class2 Tinned Copper Conductor

2

Insulation

XLPE

3

Bedding

PVC/ST2

4

Armour layer

Galvanised steel wire armour with copper earth wires and a galvanized steel tape counter helix

5

Outer Sheath

PVC/ST2

2. Cable identification

Core identification: Three cores: Black, Brown, Grey

Sheath color: Black

3. Standard compliance

IEC 60502-1, IEC 60228:2023

4.Application

S/N

Item

Technical requirement

1

Rated voltage

AC 0.6/1kV

2

Operating temperature

'-15~90℃

3

Allowed bending radius for laying

≥12 times the outer diameter of the cable

S/N

No. of cores × sectional area

Structure of conductor

Approx. dia. of conductor

Nominal thk. of insulation

Nominal thk.of sheath

Approx. OD of cable

Approx. weight of cable

 

no.× sqmm

no./mm

mm

mm

mm

mm

kg/km

1

3×35

7/2.50

7.0

0.9

1.8

28.8±2.0

2117

5. Electrical characteristics

S/N

No. of cores × sectional area ×

Max. DC resistance of conductor@20℃
20℃

Voltage withstand test

 

no.× sqmm

Ω/km

kV/min,no breakdown

1

3×35

0.529

3.5/5

 

Huayu Steel Wire Armored Power Cable Benefit

 

  • Designed for underground, industrial and outdoor power transmission circuits
  • Multi-core copper conductors endure harsh outdoor and coastal conditions
  • Stable insulation works well in damp, salt-spray and oily environments -Heavy-duty outer sheath resists moisture and chemical splashes
  • SWA steel wire armour protects against impact, crushing and rodent damage
  • LSZH / flame-retardant types meet local power safety standards
  • Each batch completes full electrical tests before delivery
1

 

FAQs

 

Q: Can this cable be direct buried without additional ducting?

A: Yes. The steel wire armor is rated for direct burial. Standard practice is still to lay it on a sand bed with warning tape above, per local code.

Q: Is the earth wire sized the same as the phase conductors?

A: No - the copper earth wire is sized separately per fault current requirements, not matched 1:1 to the phase conductor size. Confirm the fault rating with us if your site has specific short-circuit protection needs.

Q: What's the difference between this and standard SWA cable without an earth wire?

A: Standard SWA uses the armor itself as the earth path, which works but has higher impedance. The added copper earth wire here gives a dedicated low-impedance path, useful where fault clearance time is tightly regulated.

 

Hot Tags: bs 5467 armored power cable, China bs 5467 armored power cable manufacturers, suppliers, factory, 0 6 1KV Low Voltage Power Cable, BS 5467 Armored Power Cable, H07RN F Heavy Duty Rubber Cable, Industrial Low Voltage Power Cable, Low Voltage Underground Cable, Steel Wire Armored Power Cable