Key Features
This is a 0.6/1(1.2)kV industrial power cable in a three-phase-plus-neutral configuration (3×185+1×95), with an aluminum conductor, XLPE insulation, and PVC/ST2 sheath.
Three-Phase-Plus-Neutral, Unequal Neutral Size
The three phase conductors are equal in size, with a smaller neutral. Under perfectly balanced load, the neutral theoretically carries no current. Real installations rarely hit perfect balance, though, so some imbalance current does flow through the neutral. It's usually well below what the phases carry. That's why the neutral gets sized smaller instead of matching the phases.
Aluminum Conductor
Aluminum instead of copper mostly comes down to cost on the larger main-run conductors. Works well for standard industrial distribution projects where budget matters.
XLPE Insulation
Cross-linked polyethylene. Electrical performance and thermal stability both hold up fine for standard industrial distribution work.
PVC/ST2 Sheath
No added corrosion or fire treatment. Suited to indoor runs or cable trays with some baseline protection already in place.
Application

Certificate
ISO Quality Management System Certificate
IEC 60502-1:2020, EN IEC 61000-6-1:2019,
EN IEC 61000-6-3:2021

|
1.Construction |
|||||||
|
S/N |
Construction |
Requirement |
|
||||
|
1 |
Conductor |
2 Class 2 Aluminium conductor |
|||||
|
2 |
Insulation |
XLPE |
|||||
|
3 |
Sheath |
PVC/ST2 |
|||||
|
2. Cable identification Core identification: Yellow, Green, Red, Green/Yellow (or as required by the customer) Sheath color: Black 3. Standard compliance IEC 60502-1, IEC 60228 |
|||||||
|
4.Application |
|||||||
|
S/N |
Item |
Technical requirement |
|||||
|
1 |
Rated voltage |
AC 0.6/1(1.2)kV |
|||||
|
2 |
Operating temperature |
'-15~90℃ |
|||||
|
3 |
flame-retardant properties |
≥ 15D (D: cable diameter,mm) |
|||||
|
S/N |
No. of cores × sectional area |
Structure of conductor |
Approx. dia. of conductor |
Nominal thk. of insulation |
Nominal thk.of sheath |
Approx. OD of cable |
Approx. weight of cable |
|
no.× sqmm |
no./mm |
mm |
mm |
mm |
mm |
kg/km |
|
|
1 |
3×185+1×95 |
37/2.54,19/2.54 |
16.3/11.6 |
1.6/1.1 |
2.5 |
49.4±4.5 |
2876 |
|
5. Electrical characteristics |
|||||||
|
S/N |
No. of cores × sectional area × |
Max. DC resistance of conductor@20℃ |
Voltage withstand test |
||||
|
no.× sqmm |
Ω/km |
kV/min,no breakdown |
|||||
|
1 |
3×185+1×95 |
0.0991/0.193 |
3.5/5 |
||||
Huayu Industrial Low Voltage Power Cable Benefit
- Designed for heavy-duty industrial low-voltage power transmission circuits
- Multi-core copper conductors endure harsh workshop and coastal conditions
- Durable insulation works well in damp, dusty, salt-spray and oily environments
- Heavy-duty outer sheath resists oil, chemical splashes and abrasion
- Optional SWA steel wire armour for underground & on-site mechanical protection
- LSZH / flame-retardant types meet industrial safety standards
- Each batch completes full electrical tests before delivery

FAQs
Q1: Main applications?
A: Workshops, production lines and factory power distribution systems.
Q2: Function of SWA armour?
A: Protect cables against impact, crushing and rodent damage for buried installation.
Q3: Standard voltage rating?
A: 0.6/1kV for industrial low-voltage distribution.
Q4: Flame-retardant versions available?
A: Yes, LSZH and flame-retardant options for industrial safety requirements.
Q5: Quality documents?
A: Full batch electrical tests, factory test reports are provided.
Hot Tags: industrial low voltage power cable, China industrial low voltage power cable manufacturers, suppliers, factory, BS 5467 Armored Power Cable, H07RN F Heavy Duty Rubber Cable, Industrial Low Voltage Power Cable, Low Voltage Armored Cable, low voltage cable, Low Voltage Underground Cable